Wires with steel supporting cable AVT

Wires with steel supporting cable AVT

default alt
  • Affordable prices, no markups or overpayments;
  • Stability of production and rhythm of deliveries;
  • We comply with GOSTs and all technological standards.

To find out the cost of the cable, send the order code to our managers.

Generate order code

Delivery is carried out as soon as possible after the order is placed.


Wires with a steel supporting strand according to ST RK 3410-2019

  • AVT – wires with aluminum conductors, with a steel supporting strand, insulated with polyvinyl chloride compound, designed for the transmission and distribution of electric power in power and lighting networks with a voltage of 380 V AC at a frequency of 50 Hz.

  • Climatic design type according to GOST 15150: UHL, placement category 2. Wires do not support combustion during single installation.

    Service life of wires – at least 7 years. The service life is counted from the date of manufacture of the wires.


Wire construction

  • The conductive cores of the wires are round and comply with GOST 22483: for a cross-section of (2.5-10) mm² – class 1; for a cross-section of 16 mm² – not lower than class 2. The temporary tensile strength of aluminum wires before stranding into a core is at least 88 MPa.

    The electrical resistance of the conductive core to direct current, recalculated per 1 km length at a temperature of 20 °C, does not exceed the values specified in GOST 22483.

  • The conductive core is insulated with dark-colored polyvinyl chloride compound that does not propagate fire.

    The steel supporting strand complies with GOST 3062, with a wire diameter of 0.5 mm. The insulation of the steel strand is made of dark-colored polyvinyl chloride compound that does not propagate fire. The insulated wire cores are twisted around the strand with a pitch of 12 to 16 wire diameters in the twist. The twisting direction is right-hand.


Table 1. Nominal conductor cross-section, insulation thickness, wire diameter, calculated wire mass, and permissible current loads

Number and cross-section of conductors, mm²Insulation thickness, mmStrand insulation thickness, mmNominal wire diameter, mmCalculated wire mass, kg/kmPermissible current loads of wires, AConstruction length, m
2х2.50.80.57.447.122110
2х41.00.59.365.430110
2х61.00.510.281.135110
2х101.20.512.7118.055110
2х161.21.016.1188.070110
3х2.50.80.58.462.720110
3х41.00.510.590.428110
4х2.50.80.59.578.620110
4х41.00.811.9115.028110
4х61.00.513.2146.032110
4х101.20.516.5226.042110
4х161.21.020.6348.060110