The flexible power cable GERDA-TFL is designed for use in telephone exchanges, mobile base stations, data centers, uninterruptible power supplies, and similar equipment where a cable with low inductance and high electromagnetic compatibility is required. The GERDA-TFL cable can serve as a replacement for the TFL 492 32 (Ericsson) cable.
The cable is intended for the transmission and distribution of electrical power in stationary DC installations with a nominal voltage of 600V, a nominal AC voltage of U = 380V at a frequency of 50Hz, and a maximum AC voltage of Um = 600V.
Fire-resistant “FR” cables are used for connecting devices that must remain operational in fire conditions.
GERDA-TFL is produced with multi-stranded tinned or copper “m” conductors of Class 5 according to GOST 22483-2012 (high flexibility). The conductors are flat-shaped, consisting of three parallel-laid strands of soft copper wires.
The nominal cross-section of the copper conductors: 2.5; 4; 6; 10; 16; 25 mm². By agreement with the customer, cables with a different number of conductors and nominal cross-section can be manufactured.
In fire-resistant “FR” cables, a wrapping of two mica-containing tapes is applied over the conductors, preventing them from short-circuiting in case of fire.
The conductor insulation can be made of:
One conductor is insulated in gray, the other in black.
An overall shield may be applied over the core of two flat conductors, available in the following types:
Cables may have armor under the outer sheath:
The outer sheath can be made of (see Table 3):
The color of the outer sheath is specified when ordering. If not specified, the sheath is produced in gray; for the “UF” version, the sheath is black.
Such cables have a fire hazard rating of “ng(C)-HF” or “ng(C)-FRHF” and are less flexible due to the rigid sheath.
Nominal voltage | — 600 V DC — 380 V AC at a nominal frequency of 50 Hz, maximum voltage Um = 600 V |
Insulation electrical resistance at +20°C, minimum | — 500 MΩ/km for cross-linked polyolefin “Ps” insulation — 100 MΩ/km for halogen-free polymer compositions “P” and thermoplastic elastomer “T” — 10 MΩ/km for PVC insulation |
Electrical resistance of conductive cores | Electrical resistance of conductors complies with GOST 22483-2012 |
AC voltage test at 50 Hz / 5 min | — Non-shielded cables: 2500 V — Shielded cables: 2000 V |
Operating temperature in stationary condition | from -60° to +90°C for cables with “P” index from -60° to +80°C for cables with “Ps” index from -70° to +70°C for cables with “P” index resistant to extreme cold conditions “EHL” from -60° to +125°C for cables with material “T” from -60° to +70°C for “V” cables |
Minimum installation temperature, not lower than | — minus 40°C for cables with “EHL” index — minus 30°C for other cables |
Impact resistance at low temperature | — minus 60°C for “EHL” cables — minus 40°C for other cables |
Climatic performance according to GOST 15150 | “V” version, placement category 1-5, suitable for all macroclimatic regions |
Fire resistance of cables with “FR” index | at least 180 minutes under flame exposure and temperatures of at least +750°C (PO1 as per GOST 31565) |
Resistance to mold fungi | Cables are resistant to mold fungi, biological fouling level up to grade 2 |
Seismic and vibration resistance | Maintain functionality under seismic impact of at least 7 on the MSK-64 scale. |
Minimum installation and operational bending radii inD (largest outer cable dimension), at least | — 3D for non-armored cables — 4D for wire-armored cables |
Service life, minimum | for cables with insulation and sheath made of thermoplastic elastomers “T” — at least 25 years, other cables — at least 30 years |
Warranty period | 2 years from the date of cable commissioning |
Conductor insulation material | Permissible conductor heating temperature, °C | |||
Continuous | Overload mode | Maximum in short circuit | Non-ignition in short circuit | |
“B” — PVC compound | 70 | 90 | 160 | 350 |
“P” — Halogen-free polymer composition | 90 | 100 | 170 | 350 |
“Ps” — Cross-linked polyolefin | 90 | 130 | 250 | 400 |
“T” — Thermoplastic elastomer | 125 | 150 | 200 | 350 |
Insulation material designation | Fire hazard rating | Description of sheath and insulation material, as well as cable design type according to fire hazard rating (as per GOST 31565-2012) |
V | ng(B) | cables with PVC plastic insulation and low-flammability PVC plastic sheath, non-flammable in group installations category V |
ng(B)-LS | cables with insulation and sheath made of low-fire-hazard PVC plastics, non-flammable in group installations category B, with reduced smoke and gas emission | |
ng(B)-LSLTx | cables with insulation and sheath made of low-fire-hazard PVC plastics, non-flammable in group installations category B, with reduced smoke and gas emission, and low toxicity of combustion products | |
ng(B)-FRLS | fire-resistant cables with insulation and sheath made of low-fire-hazard PVC plastics, non-flammable in group installations category B, with reduced smoke and gas emission | |
ng(B)-FRLSLTx | fire-resistant cables with insulation and sheath made of low-fire-hazard PVC plastics, non-flammable in group installations category B, with reduced smoke and gas emission, and low toxicity of combustion products | |
P | ng(B)-HF | cables with insulation and sheath made of halogen-free polymer compositions, non-flammable in group installations category B, and do not emit corrosive gaseous combustion products |
ng(B)-FRHF | fire-resistant cables with insulation and sheath made of halogen-free polymer compositions, non-flammable in group installations category B, and do not emit corrosive gaseous combustion products | |
Ps | ng(B)-LS | cables with cross-linked polyolefin insulation and low-fire-hazard PVC plastic sheath, non-flammable in group installations category B, with reduced smoke and gas emission |
ng(B)-FRLS | fire-resistant cables with cross-linked polyolefin insulation and low-fire-hazard PVC plastic sheath, non-flammable in group installations category B, with reduced smoke and gas emission | |
ng(B)-HF | cables with cross-linked polyolefin insulation and halogen-free polymer sheath, non-flammable in group installations category B, and do not emit corrosive gaseous combustion products | |
ng(B)-FRHF | fire-resistant cables with cross-linked polyolefin insulation and halogen-free polymer sheath, non-flammable in group installations category B, and do not emit corrosive gaseous combustion products | |
T | ng(B) | cables with insulation and sheath made of thermoplastic elastomers, non-flammable in group installations category B |
ng(B)-FR | fire-resistant cables with insulation and sheath made of thermoplastic elastomers, non-flammable in group installations category B |
* – “ZG” cable (rodent-protected) is made from “P” material with “ng(C)-HF” or “ng(C)-FRHF” rating
The diagram schematically represents the construction of the TFL 492 32 (Ericsson) cable.
The GERDA-TFL cable is a full equivalent of the TFL 492 32 cable. Table 4 provides the corresponding GERDA-TFL designation for each version of the TFL 492 32 cable.
Fire hazard rating |
ng(В) |
ng(В)-LS |
ng(В)-LSLTx |
ng(В)-HF |
ng(C)-HF |
ng(В)-FR |
ng(В)-FRLS |
ng(В)-FRLSLTx |
ng(В)-FRHF |
ng(C)-FRHF |
Conductor cross-section, mm² |
2,5; 4; 6; 10; 16; 25 |
Tinning of copper conductors | |
tinned conductors | |
m | copper conductors |
Insulation material of conductive cores | |
V | PVC compound |
P | halogen-free polymer compositions |
Ps | cross-linked polyolefin |
T | thermoplastic elastomer |
Overall shield over the core of all conductors (pairs, triples, quads) | |
no overall shield | |
E | aluminum foil tape (Alumoflex) |
Em | braid of copper wires |
El | braid of tinned copper wires |
Emf | copper foil tape |
EEl | braid of tinned copper wires over Alumoflex |
Armor under the outer sheath | |
no armor | |
K | solid wire armor of galvanized wires under the outer sheath |
Ko | braid of galvanized wires under the outer sheath |
Special execution | |
no special execution | |
UF | resistant to solar radiation, rain, dynamic abrasive dust impact, and frost formation |
EHL | resistant to extremely cold conditions (only for insulation material “P”) |
M | oil and gasoline resistance |
H | resistant to chemically aggressive environments |
ZG | sheath resistant to damage by rodents, ants, and termites |
2 x
–
TU 27.32.13-044-76960731-2020
Example of cable designation when ordering | Description |
GERDA-TFL ng(B)-HF 2×10 PEEl-UF TU 27.32.13-044-76960731-2020 | Flexible power cable for telecommunications equipment, with two tinned copper conductors of 10 mm² nominal cross-section, insulation and sheath made of halogen-free polymer compositions, flame-retardant in group installations according to category B, not emitting corrosive gaseous products, with an overall screen of aluminum foil tape, over which a braid of tinned copper wires is applied. The sheath is resistant to solar radiation, black in color, operating temperature range -60°…+90°C. |
TFL 49232 Part no. | GERDA-TFL cable designation | Number of conductors x cross-section (AWG) | Nominal cable size by sheath, W x H, mm | Conductor electrical resistance, Ohm/km, max | Conductor insulation color | Sheath color | Weight, kg/km |
TFL 492 322 | GERDA-TFL ng(B)-HF 2×2.5 PEEl | 2×2.5 mm² (2×14 AWG) | 7.3×7.0 | 8.21 | black, gray | gray | 100 |
TFL 492 324 | GERDA-TFL ng(B)-HF 2×6 PEEl | 2×6 mm² (2×10 AWG) | 9.4×9.4 | 3.39 | black, gray | gray | 193 |
TFL 492 324/0 | GERDA-TFL ng(B)-HF 2×6 PEEl-UF | 2×6 mm² (2×10 AWG) | 9.4×9.4 | 3.39 | black, gray | black | 193 |
TFL 492 325 | GERDA-TFL ng(B)-HF 2×10 PEEl | 2×10 mm² (2×8 AWG) | 10.5×11.5 | 1.95 | black, gray | gray | 292 |
TFL 492 325/0 | GERDA-TFL ng(B)-HF 2×10 PEEl-UF | 2×10 mm² (2×8 AWG) | 10.5×11.5 | 1.95 | black, gray | black | 292 |
TFL 492 326/0 | GERDA-TFL ng(B)-HF 2×16 PEEl-UF | 2×16 mm² (2×6 AWG) | 11.8×13.6 | 1.24 | black, gray | black | 426 |