Why Shields and Armor Are Grounded: Different Functions
A shield and armor solve different tasks, and confusing their purpose is the first source of installation errors. A shield is electromagnetic protection. It controls the field: it reduces the influence of external interference on the signal in the conductors and limits the emission of the cable itself. Grounding the shield turns it into a controlled conductor through which induced currents flow to earth without creating a potential difference across the conductors.
Armor is mechanical protection. Steel tape or wire protects the cable from damage during installation and operation. At the same time, armor is part of the protective grounding circuit: if insulation is damaged, it participates in diverting current and equalizing potentials. PUE 1.7.76 directly classifies metal sheaths and armor of control and power cables as parts subject to grounding or neutral grounding.
The practical conclusion: the shield is grounded for EMC and signal quality, the armor for electrical safety and potential equalization. The schemes may coincide, but the rationale is different. The construction of a power cable with shield and armor is discussed in the material power cable: construction, types, and characteristics.
Single-Point and Two-Point Shield Grounding
Single-point grounding means the shield is connected to earth at only one point. This scheme breaks the loop for power-frequency currents induced in the shield under asymmetry or external magnetic fields. For cable lines up to 1 km long, single-point shield grounding is considered a standard solution. At the ungrounded end of the shield, a voltage relative to earth is induced, so all work on the sheath and shield is performed only on a de-energized line.
Two-point grounding connects the shield to earth at both ends. This scheme is used where it is important to reduce shield impedance for high-frequency interference and where a reliable path is needed for short-circuit current through the shield. The price is stray currents in the shield that reduce cable capacity and create additional heating. For single-core power cables at medium and high voltage, solid two-point grounding of shields without transposition leads to noticeable losses, so designers choose between single-point grounding, transposition, and shield sectionalization.
There is no universal rule that “the shield is always grounded on one side.” The choice depends on the line purpose, interference frequency range, route length, cable construction, and project requirements. For low-frequency signals (up to a few megahertz), single-point grounding that breaks the loop is preferable. For high-frequency interference and digital lines, multi-point grounding with low impedance is more effective, up to a circumferential connection of the shield to the enclosure at both ends. Requirements for installing shielded cables in control networks are detailed in the material control cable installation.
Grounding Schemes in Words
Single-Point Shield Grounding
The cable shield is connected to the grounding bus at one end of the line. The other end of the shield remains isolated from earth. An induced voltage appears at the ungrounded end, so the end is protected with an insulating cap or connected through a surge arrester if required by the project. This scheme is used for control and signal lines with low-frequency signals, as well as for power cables where it is important to exclude circulating currents in the shield.
Two-Point Shield Grounding
The shield is connected to the grounding device at both ends of the cable. This scheme reduces shield impedance at high frequencies and provides a path for interference currents. To prevent loops and equalize potentials between grounding points, a parallel grounding conductor is laid or a potential equalization circuit is used. Two-point grounding is not permitted in the presence of strong magnetic fields where dangerous power-frequency voltage is induced in the shield loop.
Armor Grounding Through Terminations
When making a termination, the armor and metal sheath of the cable are connected to the potential equalization circuit with a flexible copper conductor. The conductor is applied with a braided end to the armor and sheath along the cable axis, and the other end is routed to the grounding bolt. At joints and terminations, the armor and shield of power cables are connected to each other. In hazardous areas, the connection of armor and sheath is performed in accordance with the equipment’s explosion protection type and project documentation requirements. Restoration of shield and armor in joints is discussed in detail in the material power cable connection.
Table: Line Type, What Is Grounded, Scheme, Risk
| Line type | What is grounded | Typical scheme | Main risk of error |
| Control, low-frequency signal | Shield | Single-point grounding on the signal source or receiver side | Two-point grounding creates a loop and interference; the shield becomes an antenna |
| Control, high-frequency signal | Shield | Two-point grounding with potential equalization | No equalization — current through the shield and signal distortion |
| Single-core power, medium/high voltage | Shield, armor | Single-point grounding, transposition, or shield sectionalization | Solid two-point grounding without transposition — stray losses and heating |
| Three-core power with armor | Armor, metal sheath | Armor grounding at both ends through terminations | No armor grounding — dangerous voltage if insulation is damaged |
| Line in a hazardous area | Armor, sheath, shield | Connection to the potential equalization circuit per project | Arbitrary connection without regard to explosion protection type |
Shield Grounding in Control and Signal Lines
In control and signal lines, the shield serves to protect weak signals from external electromagnetic fields. The grounding scheme depends on the signal frequency and the presence of potential equalization between line ends. For low-frequency analog signals (up to a few megahertz), single-point grounding breaks the loop that would otherwise act as a receiving antenna. For high-frequency digital lines, shield impedance at high frequency is determined by inductance, so multi-point grounding with low impedance is more effective.
The shield of a control cable must not serve as the return conductor of the signal circuit. If the shield is used as a return conductor, a twinaxial cable is used rather than a conventional shielded cable. Connecting the shield to random metal parts of the enclosure is not permitted: the connection is made to a dedicated grounding terminal. Grades and connection of shielded control cables are detailed in the guide control cables: grades, characteristics, and connection.
Shield and Armor Grounding in Power Lines
In power cables, the shield and armor solve different tasks, but both require an electrical connection to earth. PUE 2.3.71 requires grounding or neutral grounding of cables with metal sheaths or armor, as well as cable structures on which they are laid. When grounding metal sheaths of power cables, the sheath and armor are connected with a flexible copper conductor to each other and to the joint bodies.
For single-core power cables with a shield of copper wires or tapes, the shield grounding scheme affects losses and capacity. Two-point grounding without transposition creates a current in the shield caused by the conductor’s magnetic field. This current heats the shield and reduces the cable’s permissible current. Single-point grounding or shield transposition virtually eliminates circulating losses and can increase the continuous permissible current by up to 100%. The scheme for a specific line is selected by calculation taking into account the short-circuit current and the permissible voltage at the ungrounded end of the shield.
Relation to EMC, Interference, and Loops
Shield grounding is an EMC tool, not a formality. An improperly grounded shield becomes a source of interference: the loop formed by the shield and earth receives the magnetic field and induces current in the signal conductors. To break such a loop under low-frequency interference, single-point grounding is used. For high-frequency interference, low shield impedance is more important than breaking the loop, so grounding is performed at both ends, but with potential equalization between connection points.
The length of the grounding conductor matters. A long, thin conductor has high inductance and does not pass high-frequency interference current to earth. Shielding in this case is ineffective. The shield is connected to the enclosure with a short conductor with maximum contact area, ideally a circumferential connection around the shield perimeter. The role of shielding in reducing interference from power cables to low-current lines is covered in the material distance between power and low-current cables.
Typical Mistakes
Grounding the shield at both ends without potential equalization. A current appears in the shield caused by the potential difference between grounding points. The shield heats up, the signal is distorted, and interference protection weakens.
Leaving the armor ungrounded. If insulation is damaged, dangerous voltage appears on the armor. Armor is part of the protective grounding circuit, and its connection to earth is mandatory at line ends.
Using the shield as a signal return conductor. The shield is not intended for operating current flow. For the return current, a separate conductor or twinaxial cable is used.
Connecting the shield to random metal parts. Connecting to the enclosure or tray without a dedicated grounding point creates an unpredictable current path and worsens EMC.
Grounding with a long, thin conductor. The high inductance of such a conductor does not pass high-frequency interference to earth, and the shield stops working.
Ignoring project requirements for hazardous areas. Connection of armor and sheath in hazardous areas is performed per project and taking into account the explosion protection type, not by a standard scheme.
Checking Shield and Armor Integrity
Shield integrity is checked by measuring resistance between the shield at one end of the line and the shield at the other end. To do this, the line is de-energized, voltage is removed, and an ohmmeter or milliohmmeter is used. The resistance must correspond to the shield resistance along the cable length. A broken shield or poor contact at the connection point will show an elevated resistance.
Armor integrity is checked similarly: resistance is measured between the armor at the line ends. Additionally, terminations and joints are inspected for corrosion, loose clamps, and damage to the grounding conductor. The resistance of the grounding device is measured in accordance with PUE requirements for the specific type of electrical installation. For high-voltage cable lines, the rated resistance of the grounding device is no more than 0.5 Ohm.
FAQ
Is the shield always grounded on one side?
No. Single-point grounding is used for low-frequency signals and for lines where currents in the shield must be excluded. For high-frequency interference and digital lines, two-point grounding with potential equalization is more effective. The scheme depends on the line purpose, interference frequency, route length, and project requirements.
How does shield grounding differ from armor grounding?
The shield is grounded for electromagnetic protection and field control. The armor is grounded as part of the protective grounding and potential equalization circuit. The functions are different, although the electrical connection to earth is mandatory in both cases.
What happens if the shield is grounded at both ends without potential equalization?
A current appears in the shield caused by the potential difference between grounding points. The shield begins to heat up, and the level of interference in the signal conductors increases. For power cables, this leads to additional losses and reduced capacity.
Can armor be used as a grounding conductor?
Using armor or a metal sheath as the sole grounding or neutral protective conductor is prohibited. A separate conductor is used for protective grounding, and the armor is subject to grounding as a conductive part.
How to check that the shield is properly grounded?
Measure the resistance between the shield and the grounding bus at the line end. The resistance must be low and correspond to the shield length. Additionally, inspect the connection point: the conductor must be short, with reliable contact, without oxidation or loose clamps.
Sources
- Electrical Installation Code (PUE), 7th edition, Chapter 1.7 — grounding and protective electrical safety measures; metal sheaths and armor of control and power cables are subject to grounding or neutral grounding (clause 1.7.76).
- PUE, Chapter 2.3 — cable lines up to 220 kV; cables with metal sheaths or armor and cable structures are subject to grounding or neutral grounding (clause 2.3.71).
- GOST R 50571.4.44-2019 (IEC 60364-4-44:2007) — protection against sudden voltage deviations and electromagnetic disturbances; requirements for grounded shields of signal and information cables.
- GOST R 56530-2015 — the shield is grounded at one point when the signal frequency is below 2 MHz and at both ends when the frequency is above 2 MHz.
- IEC 60364-4-44 — protection against electromagnetic disturbances; shield grounding schemes and potential equalization requirements.
- Technical Circular No. 15/2007 — connection of armor and metal cable sheaths when making terminations in hazardous areas.
- Siemens, PCS 7 configuration manual — shield grounding under high-frequency and low-frequency interference; requirements for short grounding conductors.
- Hydropower.ru — shield grounding schemes: single-point, two-point, transposition; limitations on line length and voltage at the ungrounded end.
- EEPIR — losses in shields of single-core cables and methods for their reduction: single-point grounding and transposition.