Normal Heating and Emergency Overheating
Any current-carrying conductor heats up — this is the Joule-Lenz law, and heating itself is not a defect. The question is whether the conductor temperature falls within the permissible range for the specific insulation type. For PVC compound, the long-term permissible conductor temperature is +70 °C, for cross-linked polyethylene — +90 °C, for rubber — +65 °C. These values are established in GOST 31996-2012 and confirmed by the Electrical Installation Code of the Republic of Kazakhstan. Exceeding the permissible temperature accelerates insulation aging: plasticizers volatilize, the material becomes brittle, and dielectric strength decreases.
Heating can be assessed in two ways. The calculation method — compare the actual current with the long-term permissible current for specific conditions: installation method, ambient temperature, number of adjacent cables. The instrumental method — measure the sheath temperature with a thermal imager or contact sensor. If the sheath is consistently hotter than 60–70 °C, this is already a signal to check the line, even if the breaker does not trip. The installation method directly affects heat dissipation: a cable in a conduit or closed trunking cools worse than one laid openly, and this is discussed in detail in the material power cable installation: selection of cross-section, mounting, connection.
Main Causes of Overheating
Line overload. The load current exceeds the long-term permissible current of the cable for actual conditions. The heat generated in the conductor cannot dissipate fast enough, and the temperature rises. Overload can be continuous (consumers added without recalculating the line) or short-term (motor starting currents, simultaneous switching on of high-power equipment). The circuit breaker protects against overcurrent, but its rating may be higher than the permissible cable current. How to correctly correlate load power, current, and cross-section for 220 and 380 V networks is shown step by step in the article cable cross-section calculation by power and current: 220 and 380 V.
Insufficient conductor cross-section. The cross-section is selected based on power without corrections for temperature, installation method, line length, or number of cables in a bundle. Or the actual cross-section is understated by the manufacturer. In both cases, the conductor resistance is higher than calculated, losses and heating are greater. The actual cross-section can be checked by measuring the DC resistance of the conductor and comparing it with the standard according to GOST 22483-2021 for the corresponding class and material.
Poor contact in a terminal, lug, or joint. The contact resistance at the connection point is higher than that of a solid conductor, and additional heat is generated at the contact point. Over time, oxidation and loosening of the clamp intensify heating. This is one of the most fire-hazardous causes: local overheating can ignite insulation and adjacent materials even if the line itself operates “normally.” Requirements for the installation of joints, lugs, and terminal connections are collected in the material power cable connection: joints, installation, termination.
Improper crimping. The lug is crimped with the wrong tool, with insufficient force, or not sized for the conductor. The contact is not tight, and contact resistance increases. Externally, such a lug may look normal, but under load it heats up more than a properly made one, and a thermal imager shows this.
Group installation and insufficient cooling. Several cables laid side by side heat each other. The long-term permissible current of each cable is reduced by a factor that depends on the number of cables and the distance between them. If the factor is not taken into account, the cable operates with overload even at a seemingly “correct” cross-section. How to recalculate the permissible current taking into account adjacent cables is shown in the article group cable installation: how the permissible current load changes.
High ambient temperature. Tabulated currents are given for air at +25 °C and soil at +15 °C. In a hot workshop, attic, boiler room, or near heating equipment, a correction factor is applied that reduces the permissible current. If it is not applied, the cable will heat up at a current that would be considered permissible for normal conditions.
Damage or aging of insulation. Cracks, scuffs, moisture, and natural aging reduce the electrical strength of insulation. A leakage current occurs at the defect location, adding local heating. An old cable with dried or cracked insulation heats up more than a new one at the same load, and this can be assessed by measuring insulation resistance — the methodology is described in the article cable insulation resistance measurement with a megohmmeter: procedure and results.
Uneven phase loading. In a three-phase network with phase imbalance, a current flows through the neutral conductor that should not exist under balanced load. In networks with non-linear loads — switching power supplies, LED drivers, variable frequency drives — the current in the neutral conductor may exceed the phase current due to third harmonics. If the neutral conductor is thinner than the phase conductors, it heats up first.
Table: Where It Heats Up and What to Check
| Where it heats up | Possible cause | What to check |
| Uniformly along the entire length | Overload, insufficient cross-section, high ambient temperature, group installation | Measure current, compare with permissible for given conditions, check cross-section and factors |
| At the connection point | Poor contact, contact resistance, improper crimping | Inspect the connection, retighten terminals, check crimping quality, measure contact resistance |
| Neutral conductor hotter than phase conductors | Phase imbalance, higher harmonics, undersized neutral conductor | Measure current in phases and neutral, check neutral conductor cross-section, assess load non-linearity |
| Local section | Mechanical damage, moisture, insulation aging | Inspect the cable, measure insulation resistance, check integrity |
| In conduit or trunking | Insufficient cooling, tight packing, group installation | Check conduit fill, distance between cables, group installation factor |
Diagnostic Sequence
Diagnostics begin with measuring the actual load current using clamp meters. Compare the measured current with the long-term permissible current for the given cross-section, conductor material, and installation method. If the current exceeds the permissible value, the cause is found — overload, and the next step is to recalculate the cross-section or limit the load.
If the current is normal, check whether all correction factors were taken into account when selecting the cross-section: ambient temperature, group installation, installation method. The actual cross-section is checked by the DC resistance of the conductor. An undersized cross-section or unaccounted factors cause overheating at a formally “normal” current.
The next step is inspecting connections. De-energize the circuit, remove voltage, check terminal tightness and the condition of lugs and joints. Look for darkening, melting, and the smell of burnt insulation. Retighten contacts with a torque wrench at the torque specified by the terminal product manufacturer. If there is any doubt about crimping quality, the lug is redone — this is cheaper than a fire.
Assess the installation conditions. A cable in a conduit, trunking, or bundle cools worse than a single openly laid cable. If several cables are laid side by side, check whether the derating factor has been applied. If the ambient temperature is above the standard, check the temperature correction factor.
Additional measurements are performed when the first four steps have not identified the cause. Measure insulation resistance with a megohmmeter — it will reveal moisture, aging, or mechanical damage. Check for higher harmonics with a power quality analyzer. Assess phase imbalance. A thermal imager under load will reveal local overheating invisible during external inspection.
Why a Cable Heats Up at a Current Below the Breaker Rating
A common misconception: if the breaker does not trip, the cable is fine. The circuit breaker protects wiring from overcurrent, but its rating is selected based on the permissible cable current taking into account installation conditions. If the breaker is selected with an overstated rating, the cable may heat up at a current below the protection tripping current.
Example: a 2.5 mm² cable with PVC insulation in a wall has a permissible current of about 21 A for typical conditions. A 25 A breaker will not trip at 22–24 A, but the cable will operate with overload. Long-term heating above the permissible temperature accelerates insulation aging — the cable “ages” faster than designed.
The second cause is group installation or elevated ambient temperature. The breaker is rated for nominal current without taking these factors into account. The cable heats up because the actual permissible current is lower than the tabulated value, and the breaker “does not know” about it.
The third cause is poor contact. The breaker does not respond to local overheating at a connection if the current does not exceed the setpoint. The contact can heat up and deteriorate at normal line current.
Why Local Heating at a Connection Is Dangerous
Overheating at a connection point is more dangerous than uniform overheating along the cable length. The temperature at the contact point can be significantly higher than the sheath temperature nearby. A thermal imager shows a local “hot spot” with a temperature exceeding the permissible value for insulation, even if the average line temperature is normal.
The process develops avalanche-like. As it heats up, the metal oxidizes more intensively, contact resistance increases, and even more heat is generated. The chain can end in insulation melting, a short circuit, and fire. According to electrical expert statistics, contact resistance at a connection point is one of the main causes of fires in electrical installations.
Local overheating often goes unnoticed during external inspection. The terminal looks tight but has insufficient contact area due to oxidation, improper crimping, or material mismatch. Therefore, connections are checked not only visually but also by retightening and with a thermal imager under load. The methodology and regulatory requirements for contact connections are discussed in detail in the article power cable connection.
Typical Mistakes
Increasing the cross-section without finding the cause. If the cable heats up due to poor contact, increasing the cross-section will not solve the problem. The contact will remain hot, and the money will be wasted. Diagnostics first, replacement second.
Ignoring group installation. Several cables in one trunking or conduit heat up more than a single one. If the derating factor is not taken into account, the cable operates with overload at a formally “correct” cross-section.
Checking heating by touch. The sensation of “hot” is subjective. A temperature of 60 °C for PVC insulation may be normal, while 80 °C is already an emergency. An instrument is needed for assessment, not a hand.
Tightening terminals “by eye.” Insufficient tightening results in high contact resistance; excessive tightening deforms the conductor and terminal. The tightening torque is specified by the terminal product manufacturer.
Not checking the neutral conductor. With non-linear loads, the current in the neutral may exceed the phase current. If the neutral conductor is thinner than the phase conductors, it heats up first. Check the current in the neutral conductor, not just in the phases.
Assuming the breaker fully protects the cable. The breaker protects against overcurrent but not against poor contact, group installation, or elevated ambient temperature. The correspondence of the breaker to the cable cross-section and installation conditions is checked separately.
FAQ
What cable temperature is considered normal?
There is no universal value. For PVC insulation, the long-term permissible conductor temperature is +70 °C, for XLPE — +90 °C, for rubber — +65 °C. The sheath temperature will be lower than the conductor temperature. If the sheath is hotter than 60–70 °C, this is a reason for checking. An accurate assessment is provided by comparison with the permissible temperature for the specific insulation type.
Why does the cable heat up if the breaker does not trip?
The breaker protects against overcurrent, but its rating may be higher than the permissible cable current for actual conditions. Also, the breaker does not respond to poor contact, group installation, or elevated ambient temperature. The cable may heat up at a current below the protection tripping current.
Can increasing the cross-section stop the cable from heating up?
Only if the cause is overload or insufficient cross-section. If the cable heats up due to poor contact, increasing the cross-section will not help: the contact will remain hot. The cause must be found first.
How to check connection heating without a thermal imager?
De-energize the circuit, remove voltage, and check terminal tightness with a torque wrench. Inspect the contact for darkening and melting. After energizing under load, you can measure the voltage drop across the connection: the higher the drop, the greater the contact resistance and heating. A thermal imager provides a more visual picture.
Why does the neutral conductor heat up more than the phase conductors?
With unbalanced phase loading or the presence of non-linear loads (switching power supplies, LED drivers), a current flows through the neutral conductor that should not exist under balanced load. Third harmonics sum in the neutral. If the neutral conductor cross-section is smaller than the phase cross-section, overheating is intensified. Check the current in the neutral and the neutral conductor cross-section.
Sources
- Electrical Installation Code of the Republic of Kazakhstan 2015, as amended by Order of the Minister of Energy of the Republic of Kazakhstan No. 340 dated 31.10.2022 — in force — IPS “Adilet”, adilet.zan.kz — permissible conductor temperatures, group installation factors, requirements for neutral conductors.
- GOST 31996-2012 “Power cables with plastic insulation for rated voltage 0.66; 1 and 3 kV” — in force — Table 18 — long-term permissible conductor temperatures: PVC 70 °C, XLPE 90 °C, in overload mode 90 and 130 °C respectively.
- GOST 22483-2021 “Conductors for cables, wires and cords” — in force — conductor resistance standards, actual cross-section verification.
- IEEE 519-2022 “IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems” — in force — IEEE — effect of higher harmonics on neutral conductor current.
- IEC 60364-5-52:2009 “Low-voltage electrical installations — Part 5-52: Selection and erection of electrical equipment — Wiring systems” — in force — IEC — group installation factors, temperature corrections.