Group laying of cables: how does the permissible current load change?

  • calendar-icon
    07-10-2026, 2026
  • user-icon
    Alexey Krasikov
  • clock-circle-icon
    2 минуты
article preview photo
article preview photo

Why the Current Load Is Reduced

During grouped laying, several cables are located at a close distance from each other. The heat released by each conductor as current flows is not dissipated into the environment as effectively as with a single cable. Neighbouring cables heat each other, and the total insulation temperature rises. So that the temperature does not exceed the permissible value for the given insulation type, the current load of each cable in the group is reduced by a certain coefficient.

The permissible continuous current of a single cable in the tables of the PUE RK and GOST is given for standardised conditions: air temperature +25 °C, ground +15 °C, single laying, absence of additional heating. Grouped laying is one of the deviations from these conditions, which is taken into account by introducing a reducing coefficient. The final value of the permissible current is determined by the formula:

Iperm.group = Iperm × Kgr

where Iperm.group is the permissible continuous current for the cable in the group, A; Iperm is the tabulated permissible current of a single cable for the same laying conditions (conductor material, insulation type, installation method), A; Kgr is the reduction coefficient for the specific grouped laying conditions.

If the cable has already been selected by heating from the working current, the check is performed according to the condition Idesign ≤ Iperm.group. If the condition is not met, the cross-section is increased. The general principles of cross-section selection by heating are described in the material power cable installation. The design and structural features of cables affecting heating and cooling are analysed in the article power cable: design, types, characteristics.

What the Coefficient Depends On

The reduction coefficient is not a universal number. Its value is determined by a combination of factors.

Laying method. Cables in the ground, in pipes, in ducts, in trays and openly cool differently. In the ground the heat flux goes into the soil, but during grouped laying neighbouring cables heat each other. In a pipe, the air is an additional thermal resistance. On an open tray, cooling is better than in a closed duct.

Number of cables laid together. The more cables in the group, the stronger the mutual heating and the lower the coefficient.

Distance between cables. The closer the cables are located, the worse the cooling. At a distance of 100 mm the reduction is smaller than when they touch. If the cables are spaced at a significant distance, the coefficient may not be applied.

Relative arrangement. Cables in a single layer on a tray heat each other less than cables laid in bundles or in several layers. A triangular arrangement (for single-core cables) gives a different coefficient than single-row laying.

Cooling conditions. Ambient temperature, presence of ventilation, soil thermal resistance, material of the tray or pipe. With poor cooling, the coefficient is lower.

It is important to emphasise: the coefficient cannot be chosen only by the number of cables. Two cables in the ground at a distance of 100 mm and two cables laid tightly in one pipe have different reduction coefficients.

How to Choose the Coefficient Correctly

The values of the reduction coefficients are given in the PUE RK and in GOST IEC 60364-5-52 (in Kazakhstan applied as ST RK IEC 60364-5-52). The choice depends on the laying method.

For cables laid in the ground (including laying in pipes), Table 1.3.26 of the PUE is applied. The coefficient depends on the distance between cables in clear and their number. Reserve cables are not taken into account in the calculation. The values for copper and aluminium conductors are taken as the same.

Table 1. Correction coefficient for the number of working cables lying next to each other in the ground (in pipes or without pipes), according to Table 1.3.26 of the PUE
Distance between cables in clear, mm 1 cable 2 cables 3 cables 4 cables 5 cables 6 cables
100 1.00 0.90 0.85 0.80 0.78 0.75
200 1.00 0.92 0.87 0.84 0.82 0.81
300 1.00 0.93 0.90 0.87 0.86 0.85

Source: Table 1.3.26 of the PUE, 6th edition. For laying in the ground at a depth of 0.7–1.0 m at a ground temperature of +15 °C and a specific resistance of 120 cm·K/W.

For cables laid in ducts and trays in bundles, Table 1.3.12 of the PUE is applied. The permissible currents are taken as for single cables laid openly, with the introduction of reduction coefficients. For example, for multi-layer and bundled laying, for 5–6 single-core cables the coefficient is 0.85, for 7–9 — 0.75, for 10–11 — 0.7, for 12–14 — 0.65, for 15–18 — 0.6. For single-layer laying, for 2–4 cables the coefficient is 0.67, for 5 cables — 0.6.

GOST IEC 60364-5-52 (ST RK IEC 60364-5-52) provides separate tables for different laying methods. Table B.52.17 — for cables in pipes and closed ducts, Table B.52.18 — for cables laid directly in the ground, Table B.52.19 — for cables in pipes in the ground. The values in these tables take into account the number of circuits and the relative arrangement of cables. For example, for cables laid in a single layer on an unperforated tray, with four additional cables the coefficient is 0.73.

When choosing a coefficient, it is important to check for which conditions the tabulated value is given. If the actual conditions differ, an additional recalculation is required. For cables with different cross-sections in one group, the coefficient is calculated separately, or one is guided by the smaller cross-sections.

Calculation Example

Example 1. Laying in the ground.

Three-phase 380 V line, design current Idesign = 55 A. Cable with copper conductors, PVC insulation, laid in the ground. By heating, a cross-section of 16 mm² with a tabulated permissible current Iperm = 90 A has been preliminarily selected (for standardised conditions: +15 °C, single cable).

In the same trench at a distance of 100 mm, two more loaded cables are laid. According to Table 1.3.26 of the PUE, for three cables at a distance of 100 mm the coefficient Kgr = 0.85.

Iperm.group = 90 × 0.85 = 76.5 A.

The condition Idesign = 55 A ≤ Iperm.group = 76.5 A is met. The cross-section of 16 mm² passes.

Example 2. Laying in a duct.

A group of six single-core copper cables with a cross-section of 10 mm² is laid in a duct in bundles. The tabulated permissible current for a single cable laid openly is 80 A (according to Table 1.3.4 of the PUE). According to Table 1.3.12 of the PUE, for 5–6 single-core cables with multi-layer and bundled laying, the coefficient Kgr = 0.85.

Iperm.group = 80 × 0.85 = 68 A.

If the design current of one cable exceeds 68 A, the cross-section is increased. If the design current is lower, a cross-section of 10 mm² is suitable.

In both examples, the coefficients are taken from the PUE tables. If the designer calculates according to GOST IEC 60364-5-52, the tables of that standard are used. Mixing tables from different normative systems is not permitted.

Grouped Laying in Tray, Duct and Ground

Laying in the ground. Cooling of cables in the ground depends on the thermal resistance of the soil. The standardised value is 2.5 K·m/W. At higher resistance (dry sand, rocky soil), an additional coefficient is introduced according to Table B.52.16 of GOST IEC 60364-5-52. The laying depth also affects cooling. For cables in the ground, the reduction coefficient depends on the distance between cables: at 100 mm — 0.85 for three cables, at 300 mm — 0.90. Reserve cables are not taken into account.

Laying in a duct. The duct encloses the cables, and heat removal occurs through the walls of the duct. The more densely the cables are laid, the worse the cooling. With multi-layer and bundled laying, the coefficient is lower than with single-layer. For 12–14 single-core cables in a duct, the coefficient is 0.65. With single-layer laying of 2–4 cables — 0.67. The specific values are given in Table 1.3.12 of the PUE.

Laying on a tray. Perforated trays provide better cooling than closed ducts due to ventilation. Unperforated trays are inferior in cooling. GOST IEC 60364-5-52 provides separate tables for different types of trays. For cables laid in a single layer on an unperforated tray, with four additional cables the coefficient is 0.73. When cables are arranged with gaps, cooling is better, and the coefficient is higher.

For laying cables in pipes in the ground, Table B.52.19 of GOST IEC 60364-5-52 is applied. When laying several cables in one pipe, the coefficient is lower than when laying in separate pipes at a distance. The internal diameter of the pipe also affects cooling: the more densely the pipe is filled, the worse the heat removal.

Typical Mistakes

Choosing the coefficient only by the number of cables. Two cables in the ground at a distance of 300 mm and two cables in one pipe have different coefficients. The laying method and relative arrangement affect it no less than the number.

Applying the coefficient for single laying. If the cable is laid singly, the coefficient is not introduced. Introducing a reducing coefficient “just in case” leads to an unjustified increase in cross-section and a rise in the cost of the line.

Using PUE and GOST IEC tables at the same time. Coefficients from different systems have different base conditions. They cannot be multiplied or chosen arbitrarily. If the calculation is carried out according to the PUE, the PUE tables are used; if according to GOST IEC — the GOST IEC tables.

Ignoring reserve cables. Reserve cables are not taken into account when calculating the group coefficient. Including them in the group overstates the number of cables and understates the permissible current.

Neglecting additional coefficients. In addition to the group coefficient, a temperature coefficient and a soil thermal resistance coefficient may apply. Their product gives the final permissible current. Ignoring one of them leads to overheating of the cable.

Comparing the result with the tabulated current of a single cable. After introducing the group coefficient, the permissible current is reduced. The design current must be compared with Iperm.group, not with the tabulated value for a single cable.

FAQ

What is the grouped laying coefficient?

The grouped laying coefficient Kgr is a reducing coefficient by which the tabulated permissible current of a single cable is multiplied when laying several cables at a close distance. The values are given in the tables of the PUE RK and GOST IEC 60364-5-52.

How does the coefficient affect the choice of cross-section?

After introducing the coefficient, the permissible current of the cable in the group is reduced. If the design current exceeds Iperm.group, the cross-section is increased to a value at which the condition Idesign ≤ Iperm.group is met.

Should reserve cables be taken into account when calculating the coefficient?

No. The PUE directly states: reserve cables are not taken into account when calculating the group coefficient. Only working cables are taken into account.

Are the coefficients the same for copper and aluminium conductors?

In Table 1.3.26 of the PUE, the coefficient values for copper and aluminium conductors are taken as the same. For other tables, the notes to the specific source should be checked.

Can one coefficient be applied to the whole group?

Tabulated coefficients are calculated for groups of cables of the same size and load. If the group consists of cables of different cross-sections, the calculation is based on the permissible load of the smallest cross-section, or the coefficient is determined separately.

How to take multi-layer laying into account?

With multi-layer laying, the coefficient is lower than with single-layer. For cables in ducts and trays, the values for multi-layer laying are given in Table 1.3.12 of the PUE. For cables in the ground, multi-layer laying is encountered less often, and the coefficient is determined according to Table 1.3.26 taking into account the distance between cables.

Sources

  • Electrical Installation Code (PUE), 6th edition — Table 1.3.12 “Reduction coefficient for wires and cables laid in ducts” — in force — dokipedia.ru/document/5457376.
  • Electrical Installation Code (PUE), 6th edition — Table 1.3.26 “Correction coefficient for the number of working cables lying next to each other in the ground (in pipes or without pipes)” — in force — dokipedia.ru/document/1724750.
  • GOST IEC 60364-5-52:2011 “Low-voltage electrical installations. Part 5-52. Selection and erection of electrical equipment. Wiring systems” — Tables B.52.17–B.52.19 — in force — files.stroyinf.ru.
  • Electrical Installation Code of the Republic of Kazakhstan 2015, as amended by the order of the Minister of Energy of the Republic of Kazakhstan dated 31.10.2022 No. 340 — in force — IPS “Adilet”, adilet.zan.kz.