How to Choose a Cross-Section: A Brief Answer
The cross-section is chosen based on the larger of two results: the calculated load current with corrections for installation conditions, and the voltage drop check for the actual line length. Permissible current tables provide a starting point, but they do not replace the voltage drop check for long lines.
For a single-phase 220 V network, the calculated current is: I = P / (U · cos φ). For a three-phase 380 V network: I = P / (√3 · U · cos φ). Power is substituted in watts, voltage in volts, and the result is in amperes. The resulting current is compared with the permissible continuous current table for the chosen installation method, conductor material, and insulation type, then the table value is multiplied by correction factors.
What Data Is Needed for the Calculation
To perform the calculation, you will need:
- Load power — the sum of the rated powers of consumers that may operate simultaneously, W or kW.
- Mains voltage — 220 V (single-phase) or 380 V (three-phase).
- cos φ — power factor. For resistive loads (heaters, incandescent lamps) it is close to 1. For electric motors and transformers, it is taken from the datasheet.
- Efficiency — for motors, if the power is specified at the shaft rather than the power drawn from the mains.
- Line length — from the distribution board to the load, m.
- Installation method — open, in a pipe, in the ground, in a tray, in a bundle.
- Conductor material — copper or aluminium. The difference between copper and aluminium conductors affects the permissible current and voltage drop.
- Ambient temperature — if it differs from the rated value (+25 °C for air, +15 °C for ground).
- Number of loaded cables laid together — for group installation.
Formulas and the Principle of Calculation
Calculated Load Current
Single-phase 220 V network:
I = P / (U · cos φ)
where I is the calculated current, A; P is the active load power, W; U is the phase voltage, 220 V; cos φ is the power factor.
Three-phase 380 V network (balanced load):
I = P / (√3 · U · cos φ)
where √3 ≈ 1.732; U is the line voltage, 380 V. For a motor, if the shaft power is specified, the formula takes the form: I = Pnom / (√3 · U · cos φ · η), where η is the efficiency.
The Relationship Between Calculated Current and Permissible Continuous Current
The calculated current is the current that will flow through the cable at the given load. The permissible continuous current of the cable is a standardised value at which the conductor temperature does not exceed the permissible value for the given insulation type under specific installation conditions. The selection condition is:
Icalc ≤ Iperm · k1 · k2 · …
where Iperm is the table value of permissible continuous current; k are correction factors (temperature, group installation, etc.).
Voltage Drop Check
For a line longer than 10–15 m, the voltage drop is checked separately.
Single-phase line: ΔU = 2 · I · L · (ρ / S) · cos φ
Three-phase line: ΔU = √3 · I · L · (ρ / S) · cos φ
where ΔU is the voltage drop, V; I is the calculated current, A; L is the line length, m; ρ is the resistivity of the conductor material: for copper 0.0175 Ω·mm²/m, for aluminium 0.028 Ω·mm²/m; S is the conductor cross-section, mm²; cos φ is the power factor.
Permissible voltage drop: no more than 3 % for lighting lines and no more than 5 % for power lines — according to the PUE of the Republic of Kazakhstan.
Step-by-Step Example: From Power to Verification
Initial data. Three-phase asynchronous motor: Pnom = 15 kW at the shaft, U = 380 V, cos φ = 0.85, η = 0.88. The line from the distribution board to the motor is 80 m, laid openly in a tray together with two other loaded cables. The indoor air temperature is +35 °C. Copper conductors, PVC insulation.
Step 1. Calculated current.
I = Pnom / (√3 · U · cos φ · η) = 15,000 / (1.732 · 380 · 0.85 · 0.88) ≈ 30.4 A.
Step 2. Preliminary selection from the table.
For copper conductors with PVC insulation under open installation, the nearest cross-section by permissible current is 4 mm² (Iperm = 36 A according to Table 1.3.6 of the PUE RK for sheathed cables, open). However, 36 A is the table value for rated conditions (+25 °C, single cable).
Step 3. Correction factors.
Temperature +35 °C: for PVC insulation at a rated +25 °C, the correction factor is ≈ 0.88 (according to the PUE RK correction factor table).
Group installation: three loaded cables in a tray — reducing factor ≈ 0.85 (according to Table 1.3.26 of the PUE RK for cables laid side by side).
Adjusted permissible current: Iperm.adj = 36 · 0.88 · 0.85 ≈ 26.9 A.
The calculated current of 30.4 A exceeds 26.9 A. The 4 mm² cross-section is not suitable.
Step 4. Repeat selection.
The next cross-section is 6 mm² (Iperm = 46 A from the same table). Adjusted current: 46 · 0.88 · 0.85 ≈ 34.4 A. The condition 30.4 ≤ 34.4 is satisfied.
Step 5. Voltage drop check.
ΔU = √3 · I · L · (ρ / S) · cos φ = 1.732 · 30.4 · 80 · (0.0175 / 6) · 0.85 ≈ 12.5 V.
ΔU% = 12.5 / 380 · 100 ≈ 3.3 %.
For a power line, up to 5 % is permissible (PUE RK). The condition is satisfied.
Step 6. Result.
We adopt a cable with copper conductors of 6 mm² cross-section. The initially selected 4 mm² cross-section had to be increased due to temperature and group installation. If the line had been longer, the voltage drop could have been the deciding factor. The construction and characteristics of power cable are described in a separate article.
What Can Change the Result
| Parameter | How it affects the choice |
|---|---|
| Installation method | Open, in a pipe, in the ground — different table values of permissible current. In the ground, cooling is better than in a pipe, but worse than in open air at low ambient temperature. |
| Ambient temperature | When it deviates from the rated value (+25 °C air, +15 °C ground), a correction factor is introduced. As the temperature rises, the permissible current decreases. |
| Number of loaded conductors | A three-core cable heats up more than a single-core one at the same current. Table values for three-core cables are lower. |
| Group installation | Several cables side by side heat each other. Reducing factors are introduced (Table 1.3.26 of the PUE RK). |
| Conductor material | Copper permits a higher current for the same cross-section than aluminium. Comparison of copper and aluminium. |
| Insulation type | PVC permits conductor heating up to +70 °C, cross-linked polyethylene (XLPE) — up to +90 °C. For XLPE, permissible currents are higher. |
| Line length | Over significant lengths, voltage drop becomes decisive, and a larger cross-section may be required than by heating. |
| cos φ | At low cos φ, the current at the same active power is higher, which increases the cross-section. |
| Efficiency | For motors, the input power is higher than the shaft power, so the current is greater. |
Typical Mistakes
- Choosing from a single table without corrections. Table currents are given for rated conditions. Real installation almost always differs.
- Ignoring voltage drop. For a line of 100 m or more, the cross-section by heating may be 2.5 mm², while by voltage drop 6 mm² is required.
- Applying cos φ = 1 for motors. Asynchronous motors have cos φ = 0.7–0.9. This increases the current by 10–40 %.
- Forgetting about efficiency. Shaft power is always less than input power. For a 15 kW motor, the current will be higher than when calculated without η.
- Using outdated tables. The PUE RK 2015, as amended by Order of the Minister of Energy of the RK No. 340 dated 31.10.2022, is the current document. Referring to the USSR PUE of the 6th edition is incorrect.
- Neglecting group installation. Three cables side by side already means a 15–20 % reduction in permissible current.
A Brief Selection Algorithm
- Collect data: power, voltage, cos φ, efficiency, length, installation method, temperature, number of cables side by side.
- Calculate the current using the formula for a single-phase or three-phase network.
- Select a preliminary cross-section from the permissible current table (PUE RK, Tables 4–7 of Appendix 5), taking into account conductor material and insulation type.
- Apply correction factors for temperature and group installation. If Icalc > Iperm · k, increase the cross-section.
- Check the voltage drop. If ΔU% exceeds 3 % (lighting) or 5 % (power lines), increase the cross-section.
- Adopt the larger of the cross-sections obtained by heating and by voltage drop.
- When choosing between single-core and multi-core versions, take into account the installation conditions. Single-core or multi-core cable — a separate discussion.
FAQ
Can a cross-section be chosen by power alone, without current?
It is possible if you use ready-made “power — cross-section” tables, but they give an approximate result for typical conditions (cos φ ≈ 1, short line, single installation). For motors, long lines, and group installation, a current-based calculation is mandatory.
What voltage drop is considered permissible?
The PUE RK establishes: no more than 3 % for lighting lines and no more than 5 % for power lines. For critical consumers (e.g., motors with variable frequency drives), designers sometimes adopt stricter limits.
Why is the current for the same power lower in a 380 V network than in a 220 V network?
In a three-phase network, power is distributed across three phases, and the line voltage is √3 times higher than the phase voltage. The formula I = P / (√3 · U · cos φ) yields a lower current at the same power compared to the single-phase I = P / (U · cos φ).
How to account for cos φ for a group of different consumers?
For a group, the weighted average cos φ is taken using the formula: cos φavg = ΣPi / √( (ΣPi)² + (ΣQi)² ), where Qi is the reactive power of each consumer. For household calculations, cos φ = 0.9–0.95 is often adopted.
Is it necessary to check the cable for voltage drop if the cross-section has already been chosen by heating?
Yes, if the line length exceeds 10–15 m. For short lines (distribution board — socket in the same room), the voltage drop check usually does not change the result, but for lines of 50 m or more it becomes decisive.
Sources Used
- Electrical Installation Rules of the Republic of Kazakhstan 2015, as amended by Order of the Minister of Energy of the RK No. 340 dated 31.10.2022 — Committee for Technical Regulation and Metrology of the MIR RK — https://base.spinform.ru/show_doc.fwx?rgn=71151
- GOST R 50571.5.52-2011/IEC 60364-5-52:2009 Low-voltage electrical installations. Part 5-52. Selection and erection of electrical equipment. Wiring systems — Rosstandart — https://dokipedia.ru/document/5149532
- ST RK GOST R IEC 60227-5-2009 Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V. Flexible cables (cords) — Committee for Technical Regulation and Metrology of the MIR RK — https://informproekt.ru/docs/1200100209/
- Technical Regulation of the Customs Union TR CU 004/2011 “On the safety of low-voltage equipment” — EAEU — https://docs.eaeunion.org/docs/ru-ru/0145005