OLTS and OTDR: Two Different Instruments
After an optical line is installed, two complementary measurements are performed. The first is end-to-end attenuation (insertion loss) using an optical power meter and a light source (OLTS). The second is reflectometry (OTDR) to build a line profile and localize events. These methods answer different questions and do not replace each other.
OLTS measures the total losses between two points of the line at the operating wavelength. The light source is connected to one end, and the power meter to the other. The difference between the reference power level and the level at the line output is the end-to-end attenuation. This method reproduces the real operating conditions of the system and is considered preferable for acceptance. The procedure requirements are established by IEC 61280-4-2. For single-mode fiber, measurements are performed at 1310 nm and 1550 nm; if the line will operate in the L-band (1565–1625 nm), 1625 nm is added. For multimode fiber, 850 nm and 1300 nm are used.
OTDR sends short pulses into the fiber and records backscatter and reflections. The instrument shows the loss distribution along the line and allows each event to be seen: splice, connector, bend, break. OTDR does not measure end-to-end attenuation directly — it estimates losses from backscatter, and this estimate depends on calibration and settings. OTDR calibration procedures are described in IEC 61746-1 for single-mode and IEC 61746-2 for multimode instruments. Therefore, OTDR does not replace OLTS: it complements it by explaining where exactly the losses occurred.
End-to-End Attenuation Measurement
Before measurement, connector end faces are cleaned and inspected under a microscope with 250× or 400× magnification. A contaminated end face produces additional losses and can damage the mating connector. After cleaning, the inspection is repeated to confirm its effectiveness. The source and power meter are warmed up and zeroed against a reference cord in accordance with IEC 61280-4-2. Without zeroing, the result will include the losses of the reference cable itself and the instrument connectors.
The reference level is measured at the same wavelength at which the line will operate. Then the source is connected to one end of the line under test, and the meter to the other. The measured value is recorded in dB. The procedure is repeated in the reverse direction: attenuation must be the same in both directions. For multi-fiber cables, each fiber is measured, not just a sample.
The resulting end-to-end attenuation is compared with the calculated line budget. The budget consists of fiber attenuation, splice losses, and connector losses. For G.652 fiber, the maximum attenuation per ITU-T is 0.4 dB/km at 1310 nm and 0.35 dB/km at 1550 nm. For G.657 cable, these values are practically the same, but the fiber tolerates bends better — the comparison is given in the material G652 or G657: which single-mode fiber to choose. Typical splice losses are taken within 0.1–0.3 dB, and connector losses at 0.5–0.75 dB, but the exact standards are set by the project and the operating organization. There is no universal attenuation value for all lines: it depends on fiber type, length, number of connections, and wavelengths.
How to Read a Reflectogram
A reflectogram is a graph of backscatter level versus distance. Distance is plotted horizontally, and signal level in dB vertically. The slope of the graph between events characterizes the per-kilometer attenuation of the fiber. Sharp changes in level correspond to events on the line.
A fusion splice usually appears as a small step drop without reflection (a non-reflective event). Splice loss is estimated from the level difference before and after the step. A connector produces a reflection — a narrow peak followed by a drop corresponding to the connection loss (a reflective event). A fiber bend appears as a local increase in attenuation without noticeable reflection, often in a section where the slope changes. A break produces a strong reflection or a complete loss of signal beyond the damage point.
When analyzing a reflectogram, it is important to distinguish losses from reflection. High reflection at a connector does not always mean high losses, but it returns light to the source and can affect laser operation. A non-reflective event with high losses is a reason to suspect a poor splice or macrobend. For accurate event loss evaluation, measurements are performed from both directions: the result is taken as the half-sum of the values obtained in directions A-B and B-A. A single-direction measurement can give overstated or understated losses due to differences in backscatter characteristics.
Typical Defects
Dirty connector end faces. Dust and oil on the end face scatter and reflect light. Losses grow, and reflection increases. The defect is detected visually under a microscope and from the reflectogram (a high reflection peak). It is eliminated by cleaning according to the connector manufacturer’s instructions.
Poor splice. A splice of insufficient quality produces increased losses without reflection. A step larger than permissible is visible on the reflectogram. The cause is contamination, incorrect arc parameters, or fiber offset. Such a splice is re-spliced.
Macrobend. Bending the cable with a radius smaller than permissible causes light leakage from the core. Losses grow without reflection. It is detected on the reflectogram as a local increase in attenuation. It is eliminated by changing the route or using G.657 fiber, which is more bend-resistant — the choice is described in the article G652 or G657.
Microbends. Small irregularities at the core-cladding boundary cause scattering. Losses increase gradually and may not be localized at a single event. Microbends occur with improper cable tension or the use of low-quality materials.
Cable damage. A pinch, cut, or sheath rupture disrupts fiber integrity. A break or strong reflection is visible on the reflectogram. The damage location is localized, and the section is replaced or repaired with a joint.
Low-quality connectors. Cheap connectors with poor polishing produce high losses and reflection. The defect appears on the reflectogram as a reflection peak and a loss step. Replacing the connector or patch cord eliminates the problem.
Table: Defect — Manifestation — Detection — Action
| Defect | How it manifests | How to detect | What to do |
| Dirty end face | High reflection, increased losses | 250× microscope, reflectogram | Clean, re-inspect |
| Poor splice | Loss step without reflection | OTDR, two-direction measurement | Re-splice the joint |
| Macrobend | Local increase in attenuation | OTDR | Change the route, use G.657 |
| Microbends | Gradual increase in attenuation | OTDR, attenuation measurement | Replace the section |
| Cable damage | Break or strong reflection | OTDR, visual inspection | Localize, repair |
| Low-quality connector | Reflection peak, losses | OTDR, microscope | Replace connector or patch cord |
Preparing the Line and Instruments
Before measurement, the line is disconnected from active equipment, and connector end faces are cleaned and inspected. Instruments are warmed up and calibrated. For OTDR, it is important to select the correct pulse length and measurement range: a short pulse gives better resolution but less range. Settings are selected for the line length and expected losses.
A launch cable is connected between the OTDR and the line under test. It is needed so that the first connector of the line does not fall into the reflectometer’s dead zone and so that the loss at the first connection can be measured. A receive cable is connected after the last connector of the line. It allows the last event to be seen and confirms that the line is not damaged at the far end. Without a receive cable, the OTDR may not see damage near the end of the line. The length of the launch and receive cables is usually 1–2 km for single-mode lines, but the specific requirement depends on the instrument and the project. Route preparation and selection of cable type for installation are described in the materials communication cable installation in ground, ducts, and pipes and cable installation in ground or in air.
Measurement Report and Result Evaluation
The report must contain: line designation, fiber type, measurement wavelengths, line length, end-to-end attenuation results in both directions, and OTDR results indicating events and their losses. Reflectograms and instrument data with numbers and calibration dates are attached to the report. For each fiber, the per-kilometer attenuation and total losses are recorded.
The result is evaluated by comparison with the calculated budget and project standards. If the end-to-end attenuation exceeds the budget, the cause is sought: events on the reflectogram, connector condition, and splice quality are checked. If the OTDR shows an event with losses above permissible, it is eliminated and the measurement is repeated. The line is considered accepted when all fibers pass the attenuation requirement and no unacceptable events are present on the reflectograms. The composition of as-built documentation for optical lines is determined by RD 45.156-2000, and measurement requirements by IEC 61280-4-2 and ITU-T G.650.3.
Typical Measurement Mistakes
Using OTDR without a launch cable. The first connector of the line falls into the dead zone, and its losses are not measured. The result appears better than it actually is.
Single-direction OTDR measurement. Splice and connector losses depend on direction. A single-direction measurement can produce an error. For accurate evaluation, measurements are taken from both ends and the half-sum is used.
Measuring end-to-end attenuation without zeroing the reference cable. The result includes the losses of the reference patch cord and instrument connectors. The line attenuation appears overstated.
Dirty end faces during measurement. Dust on the end face produces additional losses and reflection. The result does not reflect the real condition of the line. Before each connection, end faces are cleaned and inspected.
Incorrect wavelength selection. Measurement at 1310 nm does not show the losses that will occur at 1550 nm. For lines operating in the L-band, 1625 nm is added.
FAQ
Does OTDR replace end-to-end attenuation measurement?
No. OTDR estimates losses from backscatter and depends on calibration. End-to-end attenuation is measured by the OLTS method (source and power meter) and reproduces the real operating conditions of the line. OTDR complements OLTS by localizing events.
Which wavelengths should be used for single-mode and multimode fiber?
For single-mode fiber — 1310 nm and 1550 nm; when operating in the L-band, 1625 nm is added. For multimode fiber — 850 nm and 1300 nm.
Why is a launch cable needed for OTDR measurement?
The launch cable brings the first connector of the line out of the reflectometer’s dead zone and allows the loss at the first connection to be measured. Without it, the result for the first connector is unreliable.
What splice losses are considered acceptable?
Typical values are 0.1–0.3 dB, but the exact standard is set by the project and the operating organization. There is no universal value: it depends on fiber type and line requirements.
What to do if end-to-end attenuation exceeds the budget?
Check the reflectogram: find events with increased losses (splices, connectors, bends). Clean or replace connectors, re-splice poor joints, and eliminate bends. After elimination, repeat the measurement.
Sources
- IEC 61280-4-2:2024 Fibre-optic communication subsystem test procedures. Part 4-2: Installed cabling plant. Single-mode attenuation and optical return loss measurements — in force — IEC — method for measuring end-to-end attenuation and optical return loss.
- IEC 61746-1:2009 Calibration of optical time-domain reflectometers (OTDR). Part 1: OTDR for single-mode fibres — in force — IEC — OTDR calibration procedures.
- IEC 61746-2:2010 Calibration of optical time-domain reflectometers (OTDR). Part 2: OTDR for multimode fibres — in force — IEC — OTDR calibration for multimode fibers.
- ITU-T G.652 Characteristics of a single-mode optical fibre and cable — in force — ITU-T — maximum attenuation 0.4 dB/km at 1310 nm, 0.35 dB/km at 1550 nm.
- ITU-T G.650.3 Assessment of installation and maintenance of optical fibre cables and cable plants — in force — ITU-T — acceptance criteria, measurement wavelengths, launch cable requirements, end-face cleaning.
- IEC 61300-3-35 Fibre optic interconnecting devices and passive components. Basic test and measurement procedures. Part 3-35: Examinations and measurements. Visual inspection of fibre optic connectors and fibre-stub transceivers — in force — IEC — visual inspection criteria for connector end faces.
- ANSI/TIA-568.0-D Generic Telecommunications Cabling for Customer Premises — in force — TIA — line budget calculation formulas, typical connector and splice losses.
- RD 45.156-2000 Composition of as-built documentation for completed construction of linear structures of backbone and intra-zonal fiber-optic transmission lines — in force — Ministry of Communications of Russia — composition of reports and data sheets for optical lines.