Atmospheric air hydrocarbon gas concentration sensor

  • Purpose

    The DZU-GERDA sensor is designed to measure the level of gas contamination in indoor and outdoor environments in areas where hydrocarbon gases and vapors may be present near process equipment, storage tanks, loading racks, trunk pipeline pumping stations, compressor stations, gas storage facilities, boiler houses, and other industrial sites.

    Sensor Description

    The operating principle of the sensor is optical-absorption, based on a dual-channel infrared photometer scheme. The sensor is manufactured in an explosion-proof version with a housing made of corrosion-resistant aluminum alloy. The sensor housing includes a cable gland and a sensor module (see photo). Atmospheric air enters the sensor’s measuring cuvette through free diffusion. A protective filter prevents dust, dirt, and precipitation from entering the measuring cuvette. The current gas concentration level is displayed on a digital indicator in the sensor housing window, while threshold exceedances are indicated by LEDs.

    The sensor performs the following functions:

    • Executes startup self-diagnosis upon power-on and periodic self-diagnosis during operation; in the event of a fault, displays the corresponding error code;
    • Measures gas contamination levels in real time;
    • Performs reliability checks of measurement results;
    • Provides a convenient maintenance mode (zero and sensitivity adjustment, threshold level configuration, etc.) using a magnetic key without dismounting the sensor, directly in the hazardous area;
    • Stores calibration data and threshold gas concentration levels in the sensor’s non-volatile memory;
    • Transmits measurement results, fault messages, and gas threshold exceedances to the upper-level system via digital or analog interface (as selected);
    • Allows connection of automation and signaling actuators directly to the sensor (in versions with relay outputs).

Ordering designation

  • DZU-GERDA

    1

    2

    3

    4

    5

    6

    1. Calibration gas:

      • “PG” – methane (natural gas)
      • “NG” – propane (associated petroleum gas)
    2. Hydrocarbon concentration measurement range:

      • 0 to 100% LEL
      • 0 to 50% LEL
    3. Operating temperature range:

      • “S” – standard: from -40 to +60 °C
      • “R” – extended: from -55 to +75 °C
    4. Explosion protection and housing type:

      • “V” – explosion-proof version, housing made of aluminum alloy
    5. Output signal type:

      • “T” – current loop 4–20 mA
      • “CM” – digital interface RS-485 with ModBus-RTU protocol
      • “CS” – digital interface RS-485 with SKZ-12-Ex-01.M1 protocol
      • “R1” – relay outputs (Threshold 1, Threshold 2, Fault) 48V, 1A
      • “R2” – relay outputs (Threshold 1, Threshold 2, Fault) 220V, 3A
      • 1/2 – Cable gland 1/2″ (for cable Ø 6–15 mm)
      • 3/4 – Cable gland 3/4″ (for cable Ø 12–20 mm)
      • blank – cable gland not installed

Main technical specifications

DZU-GERDA
ParametersValues
Explosion protection marking (GOST IEC 60079-1-2011)1 Ex d IIС T4 Gb
Hazardous area classification for sensor installationIn accordance with Ex marking and GOST IEC 60079-14-2011
Detected componentsHydrocarbon gases and vapors
Measurement range of concentrationsFrom 0 to 99% LEL
Indicationmeasured concentration2-digit seven-segment display
threshold exceedance2 red LEDs (Threshold 1, Threshold 2)
failure1 red LED (Failure)
Alarm threshold rangeFrom 0 to 99% LEL
Basic measurement error limits Dо± 5% LEL
Response time t(90), max14 s
Warm-up time (startup), max1 min (10 min for extended temperature range)
DC supply voltageFrom 10 to 28 V (nominal 24 V)
Power consumption, max3 W (5 W for extended temperature range)
Output signal type (specified when ordering)analog *4—20 mA, 3- or 4-wire connection scheme (including sensor 24V power wires);
service data transmitted in the 0–4 mA range;
maximum communication line resistance 700 Ohm
digital **RS-485 interface with protocol (selectable):
– ModBus-RTU
– SKZ-12-Ex-01.M1
– HART
maximum communication line length 1200 m
relay *** R1 R2“dry” relay contacts (Threshold 1, Threshold 2, Failure):
— switching capacity 1 A/48 V DC,
— switching capacity 3 A/250 V AC
Ambient temperaturestandard rangeFrom –40 to +60 °C
extended rangeFrom –55 to +75 °C
Ingress protection rating (IP code)IP65
Relative humidity at 35 °Cup to 95% without condensation
Overall dimensions (WxHxD)220 × 242 × 140 mm
Calibration interval1 year
Weight, max3 kg
Designated service lifeSensor5 years
Detector10 years
Warranty period2 years

It is recommended to use the following cables for DZU-GERDA connection:

*
– unarmored cable KUIN ng 2×2×1.0 VE
– armored cable KUIN ng 2×2×1.0 VEK

**
– unarmored cable KVIP ng 2×2×1.0 VEl
– armored cable KVIP ng 2×2×1.0 VElK

*** for connection of power wires, Threshold 1 and Threshold 2 signals:
– unarmored cable KUIN ng 6×1.0 VE
– armored cable KUIN ng 6×1.0 VEK

Note: For other conductor cross-sections, sheath and insulation materials of KUIN and KVIP cables, refer to separate cable brochures.