Flame Fire Detector IP 330-GERDA

Flame Fire Detector IP 330-GERDA

default alt
  • Affordable prices, no markups or overpayments;
  • Stability of production and rhythm of deliveries;
  • We comply with GOSTs and all technological standards.

To find out the cost of the cable, send the order code to our managers.

Generate order code

Delivery is carried out as soon as possible after the order is placed.



Description

    • The detector is easily integrated into the customer’s fire alarm system thanks to a wide range of standardized output signal types:

      • 4-wire loop;
      • analog 4–20 mA;
      • RS-485 interface (ModBus RTU);
    • Reliable protection against false triggering even under high ambient light conditions (welding, sunlight, etc.)
    • The detector belongs to flame sensitivity Class 1
    • Red fire alarm indicator on the detector housing
    • Wide operating temperature range from –60°C to +85°C (extended range version “R”)
    • Housing resistant to various types of chemical corrosion (salt, alkaline, acidic)

Purpose and description of the detector

  • The IP 330-GERDA detector is designed to detect flame sources by their characteristic infrared radiation, registered in three spectral wavelength ranges, which enhances noise immunity and eliminates the possibility of false alarms, removing the need for an ultraviolet detection channel. The fire alarm signal is transmitted to fire alarm control panels and/or automation systems.

    The IP 330-GERDA is intended for operation in hazardous areas of classes 1 and 2 according to GOST R 51330.9 (B-1A, B-1G in accordance with Chapter 7.3 of the Electrical Installation Code) in indoor facilities and outdoor installations (such as tank farms, filling racks, pumping stations, etc.). The detector is marked with explosion protection rating 1Ex d ib IIC T4 Gb.

    The IP 330-GERDA is oriented toward the most likely direction of flame appearance, taking into account a stable detection range of 25 meters and a viewing angle of at least 90°.

    Structurally, the detector consists of a housing mounted on a swivel bracket. The housing is made of a corrosion-resistant modified aluminum-silicon alloy. It is resistant to various types of chemical corrosion (salt, alkaline, acidic). Inside the housing are optical sensors and electronic modules. The cable is routed into the housing through an explosion-proof cable gland.

  • The IP 330-GERDA detector is available in the following versions:

    • 1. By output interface:

      • Four-wire loop;
      • Current loop;
      • Digital interface RS-485 (ModBus RTU protocol).
    • 2. By operating temperature range:

      • “S” standard (-40°C to +60°C);
      • “R” extended (-60°C to +85°C);
    GERDA–KSN–FR fire-resistant junction box
    Test scheme for the flame fire detector using the GERDA-TF test flashlight

Test flashlight TF-GERDA

Purpose and application area

  • GERDA–KSN–FR fire-resistant junction box
    Test flashlight TF-GERDA
  • The TF-GERDA test flashlight is designed for testing the operability of IP 330-GERDA flame fire detectors. The testing is performed remotely, without dismantling the flame detector.

    The TF-GERDA can be used in hazardous areas.

    • Remote testing of the flame detector without dismantling
    • Rechargeable battery with charge level indication
    • Built-in laser pointer for precise targeting of the flame detector
    • Explosion protection marking: 1Ex d e ib op is IIB T4 Gb

Operation description

  • Activation and control of operating modes are carried out using a button located on the body of the TF-GERDA test flashlight. Before use, the battery charge level of the TF-GERDA must be checked. If necessary, the battery should be removed and charged outside the hazardous area. The charge level can be checked when the TF-GERDA is turned on: if fully charged, the built-in laser pointer will blink four times; two minutes before full discharge, the laser pointer will start flashing short pulses every 3 seconds.

    To test the operability of the IP 330-GERDA flame detector, switch on the TF-GERDA test flashlight and aim it toward the detector from a distance of 0.3 to 5 meters. The laser pointer enables precise alignment of the flashlight with the flame detector. After TF-GERDA is turned on, the infrared emitter starts blinking at a specific frequency, simulating flame flicker. Within 5–10 seconds, the IP 330-GERDA should trigger, and a red LED will light up on its panel.


Parameters

ParameterValue
Explosion protection marking of the test radiation source1Ex d e ib op is IIB T4 Gb
Ambient temperature-20…+40°C
Relative humidity95% (at 35°C)
Atmospheric pressure84 kPa…106.7 kPa
Ingress protection rating (IP code)IP65
DimensionsØ106 x 224 mm
Product weightno more than 1.2 kg
Power supply voltage of built-in rechargeable battery7.2…9 V (6 Ni-MH cells 1.2 V each)
Charging timeno more than 4.5 hours
Operating time with fully charged batteryat least 6 hours
Service lifeat least 5 years
Warranty period18 months

For connection of the IP 330-GERDA, it is recommended to use the armored cable KUIN ng-LS 2x2x1.0 VEK. The cables have GOST R certification, Fire Safety certification, and a ROSTEKHNADZOR permit for use in hazardous areas.